Description

Surge protector AC type 1+2 DS132RS-230 is a modular, single-phase surge protector designed for 230 V AC installations (TT/TN systems), combining type 1 and 2 protection. The device provides protection for common and differential surge modes between L/N and N/PE, with a nominal discharge current of 20 kA (15/8/20 µs) and a total lightning impulse discharge capacity of 25 kA (10/350 µs). The version with remote signaling (DS132RS-230/G) offers a changeover contact for remote monitoring of the module's status.

Manufacturer Information

Manufacturer: CITEL, a French supplier of surge protection devices. Manufacturer contact details provided in the datasheet: CITEL, 2 rue Troyon, 92316 Sèvres Cedex, France; phone +33 1 41 23 50 23; email contact@citel.fr. Devices comply with IEC 61643-11/EN 61643-11 and UL1449 ed.4 standards and have EAC and TUV certifications.

Selected Electrical Parameters

  • SPD type: 1+2 (according to IEC tests)
  • Rated voltage: Un = 230 Vac
  • Max. operating voltage AC: Uc = 255 Vac
  • Nominal discharge current: In = 20 kA (15/8/20 µs)
  • Max. discharge current per pole (8/20 µs): Imax = 50 kA
  • Lightning impulse per pole (10/350 µs): Iimp = 12.5 kA; total Itotal = 25 kA (10/350 µs)
  • Protection level L/N at In (8/20 µs): Up L/N = 1.3 kV
  • Withstand temporary overvoltage (TOV) 5 s: 335 Vac (withstands without disconnection)
  • TOV 120 min: 440 Vac (disconnection)
  • Protection modes and connections: L/N and N/PE; common and differential protection

Mechanical and Installation Parameters

  • Technology: MOV (high energy varistor) + specific gas discharge lamp (GSG) + thermal fuse
  • SPD configuration: single-phase, plug-in module
  • Mounting: on a 35 mm symmetrical rail (EN 60715)
  • Enclosure: thermoplastic material UL94 V-0
  • Operating temperature range: -40°C to +85°C
  • Protection degree: IP20
  • Emergency mode: disconnection from AC network with mechanical disconnection indicator (one per pole)
  • Connectors: screw terminals 2.5–25 mm² or rail connection option
  • Remote signaling option: DS132RS-230/G – output for changeover contact
  • Dimensions (according to the diagram in the datasheet): width 82 mm, height 90 mm, depth 74.8 mm